  • CHECK SYNCHRONISM RELAY KAVS 100 / MAVS 01 " ALSTOM / AREVA"
CHECK SYNCHRONISM RELAY KAVS 100 / MAVS 01  ALSTOM / AREVA

CHECK SYNCHRONISM RELAY KAVS 100 / MAVS 01 ALSTOM / AREVA

Update Terakhir 15 / 12 / 2019
Minimal Pembelian 0

Harga

CALL
Bagikan
DESKRIPSI PRODUK

Detail CHECK SYNCHRONISM RELAY KAVS 100 / MAVS 01 ALSTOM / AREVA

Functions Check synchronising The relay checks that the two part of the system are in synchronism by measuring the angle and the slip frequency between the line voltage and the bus voltage. Auto-reclose is blocked if these values exceed the phase angle and slip frequency settings. Manual closure is blocked if these values exceed the system angle and system slip settings. Selectable undervoltage and differential voltage measurements are available to block closure if the line and bus voltages are not compatible. To allow the circuit breaker to be closed onto an uncharged line, live line/ dead bus, dead line/ dead bus and dead line/ live bus detectors are included. These allow reclosure when the voltage on the line and/ or the bus VT is below a preset value.